72800A Systevo Control IP+

Product information "72800A Systevo Control IP+"
Systevo central unit in aP-/rack version as central unit for an organizational unit such as station or living area.

Use of System Release V12 to comply with VDE 0834-1: 2016-06 in conjunction with parent system license.
Also required to activate the system functions (e.g. mobile call query, system size, etc.).
Central unit with fieldbus interface for the management of max. 127 active system components on the room bus such as room terminals, room electronics modules, information displays and other units. The room bus can be segmented into up to six subgroups.
Management of max. 40 IP subscribers via ETH-LAN as IP touch terminals for extended service features.
Bus termination option for room bus termination (data/audio).
Additional repeaters (data/audio) required after 64 active system components. Possibility of firmware update of active system components (if supported by the units).
Monitoring and synchronisation of all data traffic as well as audio connections (calls, announcements) within the organisational unit and coordination of communication to other control centres via IP interface (ETH-LAN / station bus).
In addition, control of display displays and audible call notifications, according to defined priorities/services (interconnections) within a system installation. Flexible configuration options via the operating computer (PC) with convenient Windows GUI for call types, groups, services, group announcements, display texts, device parameters, system language, etc. depending on customer needs.
Use of a maximum of 64 control panels with up to 250 logical groups (subgroups). Networking takes place via the ETH-LAN IP interface (data/audio) or existing installations via the station bus (data/audio).
The wiring via ETH-LAN and / or fiber optic LAN takes place according to the specifications of the classic network design.
Networking is done via suitable switches / routers (ETH-LAN: IEEE802.3), which automatically detect the necessary transmission rates (10, 100, 1000MBit).
Port-based VLAN network components with QoS / ToS enable the prioritization of the light call data services over the voice services.
For security reasons (VDE 0834-1), all IP components (control panels, operating computers) work in a uniform IP address space (10.1.x.y), which is not used by other trades (e.g. GLT, medical equipment, etc.). To use a different IP address space (192.168.x.y), the configuration is done via an optional DHCP server.
Communication is based on TCP/IP via defined optical call protocols. Utilities such as Telnet, FTP are used for remote access and data transfer. Additional network applications (syslog, firewall, etc.) serve the system security and the possible analysis of stored log data.
With integrated gateway function for forwarding data/audio signals from the superior bus interface (ETH-LAN, station bus) to the room bus.
Setting up of a master control panel (with ETH-LAN: without room bus) for communication to the superior control computer via ETH-LAN and for controlling the escalation of all system messages within the entire system. Prepared for future license-dependent firmware updates to take advantage of additional service features. Central or decentralized installation (aP/rack version) in environment class I.
Project-specific planning of central equipment from 500 rooms.
  • Operation as master / slave control panel (depending on addressing / config.)
  • Communication via ETH-LAN (up to 64)
  • Terminal blocks room bus (data/audio)
  • Connecting terminals Energy supply
  • Communication interface to the active system components
  • Connection terminals Disturbance detector relays
  • USB-C connector

Service functions:
  • Software Download for Systemkomp., remote maintenance / SNMP-Fkt (with PC), basic commissioning

Security features:
  • Data retention in case of network failure acc. DIN VDE 0834 (USV required)
  • Local emergency operation
  • Sequential monitoring of the connected active components, further control panels in the system network / PC communication acc. VDE 0834-1 x Relay contact for reporting faults within the group (AS/RS)
  • galvanic isolation to other control panels by ETH-LAN connection
  • Status display via LEDs
  • Flash for data storage of the system